*1 Command is used to clear the IO-Link device backup data that is stored in the IO-Link Master Unit.
The meanings of the set values are as follows:
Set value
01 hex
Clears the IO-Link backup data.
00 hex
Does not clear the IO-Link backup data.
*2 Result is used to display the cleared status of the IO-Link device backup data that is stored in the IO-Link Master Unit.
The meanings of the values are as follows:
Set value
0000 hex
Backup completed or not executed.
0001 hex
Backup failed.
FFFF hex
Execution is in progress.
320A hex
Message timeout for IO-Link device
Sub-index 0: Number of entries
Range: −
Size: 1 byte (U8)
Sub-index 1: Session Timeout
Range: 00 to FF hex
Size: 1 byte (U8)
Digital Input Collection Setting
*1
320B hex
Sub-index 0: Number of entries
Range: −
Size: 1 byte (U8)
Sub-index 1: Port 1 Digital Input Collection Setting
Range: 00 to 01 hex
Size: 1 byte (U8)
Sub-index 2: Port 2 Digital Input Collection Setting
Range: 00 to 01 hex
Size: 1 byte (U8)
Sub-index 3: Port 3 Digital Input Collection Setting
Range: 00 to 01 hex
Size: 1 byte (U8)
Sub-index 4: Port 4 Digital Input Collection Setting
Range: 00 to 01 hex
Size: 1 byte (U8)
Sub-index 5: Port 5 Digital Input Collection Setting
Range: 00 to 01 hex
Size: 1 byte (U8)
Sub-index 6: Port 6 Digital Input Collection Setting
Range: 00 to 01 hex
Size: 1 byte (U8)
Sub-index 7: Port 7 Digital Input Collection Setting
Range: 00 to 01 hex
Size: 1 byte (U8)
Sub-index 8: Port 8 Digital Input Collection Setting
Range: 00 to 01 hex
Size: 1 byte (U8)
GX-series EtherCAT Slave Unit User's Manual
Meaning
Meaning
Unit: −
Default: 02 hex
Access: RO
Unit: −
Default: 03 hex
Access: RW
Unit: −
Default: 08 hex
Access: RO
Unit: −
Default: 00 hex
Access: RW
Unit: −
Default: 00 hex
Access: RW
Unit: −
Default: 00 hex
Access: RW
Unit: −
Default: 00 hex
Access: RW
Unit: −
Default: 00 hex
Access: RW
Unit: −
Default: 00 hex
Access: RW
Unit: −
Default: 00 hex
Access: RW
Unit: −
Default: 00 hex
Access: RW
A Appendix
Attribute: −
PDO map: Not possible
Attribute: A
PDO map: Not possible
Attribute: −
PDO map: Not possible
Attribute: R
PDO map: Not possible
Attribute: R
PDO map: Not possible
Attribute: R
PDO map: Not possible
Attribute: R
PDO map: Not possible
Attribute: R
PDO map: Not possible
Attribute: R
PDO map: Not possible
Attribute: R
PDO map: Not possible
Attribute: R
PDO map: Not possible