12 Troubleshooting and Maintenance
AL status
Name of error
code
TxPDO Setting
001E hex
Error
PDO WDT
001F hex
Setting Error
TxPDO
0024 hex
Assignment
Error
RxPDO
0025 hex
Assignment
Error
Synchronization
002C hex
Error
SYNC Signal
002D hex
Not Received
12 - 22
Contents
An error was detected in
the TxPDO settings (e.g.,
a logic setting error in the
Sync Manager).
An incorrect PDO WDT
setting was detected.
An incorrect TxPDO
setting was made (e.g., an
index, subindex, or size
that is out of range was
registered).
An incorrect RxPDO
setting was made (e.g., an
index, subindex, or size
that is out of range was
registered).
The SYNC0 interrupt
stopped during operation
in Operational state.
No SYNC0 signals have
been received since
entering DC mode.
Notification
Diagnosis
to EtherCAT
history
Master Unit
Check the Sync
Not
Can be
Manager settings in the
saved
notified
Master Unit.
Not
Can be
Check the WDT settings
saved
notified
in the Master Unit.
Check the TxPDO
Not
Can be
assignment settings in
saved
notified
the Master Unit.
Check the RxPDO
Not
Can be
assignment settings in
saved
notified
the Master Unit.
Check the
Not
Can be
synchronization settings.
saved
notified
(Encoder Input Slave
Units only)
Check the
Not
Can be
synchronization settings.
saved
notified
(Encoder Input Slave
Units only)
GX-series EtherCAT Slave Unit User's Manual
Measures