Omron GX-ID1611 User Manual page 283

Gx-series, ethercat remote i/o terminal ethercat slave units
Table of Contents

Advertisement

[L/A IN]
[PWR]
[L/A OUT]
indicator
LED
On
On
GX-series EtherCAT Slave Unit User's Manual
[RUN]
[ERR]
Description
indicator
indicator
On
F
Off
Hardware error
B
Illegal switch
setting
Non-volatile
memory data
error
B
Sync manager
setting error
Hardware error
12 Troubleshooting and Maintenance
Cause
If the error does not
clear even after the
A hardware failure
power is turned ON
occurred.
again, the Slave Unit
hardware is damaged.
Replace the Slave Unit.
The Expansion
Check the Expansion
Unit is
Unit connection.
disconnected.
Check the switch
A range setting
settings then restart the
switch or other
Slave Unit according to
switch setting is
the specification of
illegal.
connected EtherCAT
Master Unit.
Use the Configuration
Tool or SDO
communications to
A non-volatile
restore the default data
memory data error
and restart the Slave
occurred.
Unit according to the
specification of
connected EtherCAT
Master Unit.
The sync manager
Change to the correct
setting is illegal.
settings.
If the problem is not
resolved even after the
measures described
A hardware failure
above are taken, the
occurred.
Slave Unit hardware
may be damaged.
Replace the applicable
Slave Unit.
Actions
12
12 - 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents