12 Troubleshooting and Maintenance
Error
Name of error
code
Non-volatile
Memory
6330 hex
Checksum
Error
Slave
7030 hex
Hardware Error
Error codes unique to Digital I/O Slave Unit
Error
Name of error
code
Expansion Unit
5020 hex
Hardware Error
Error codes unique to Analog I/O Slave Unit
Error
Name of error
code
I/O
2130 hex
Disconnection
Detected
Switch Setting
5600 hex
Error
12 - 20
Diagnosis
Contents
history
An error occurred in
non-volatile memory
Saved
data in the Slave Unit.
A hardware error
occurred in the
Saved
EtherCAT
communications area.
Diagnosis
Contents
history
Expansion Unit
Saved
hardware errors
Diagnosis
Contents
history
A broken analog input
Not
line was detected.
saved
A range setting switch
Not
setting is illegal.
saved
Notification to
EtherCAT
Measures
Master Unit
A non-volatile memory
data error occurred.
Initialize non-volatile
memory from a
Configuration Tool or
with SDO
Can be notified
communications, and
then restart the Slave
Unit.
(Target indexes: 1011
hex Restore default
parameters
(parameter restore))
If the error occurs
even after restarting
Cannot be
the power supply, the
notified
Slave Units is
damaged. Replace the
Slave Units.
Notification to
EtherCAT
Measures
Master Unit
The Expansion Unit is
disconnected. Check
the Expansion Unit
connection.
If the error is displayed
Cannot be notified
again, the Expansion
Unit is damaged.
Replace the
Expansion Unit.
Notification to
EtherCAT
Measures
Master Unit
Check the slave
voltage or current input
Can be notified
line to see if it is
broken.
Set the range setting
switch correctly and
Can be notified
restart the Slave Unit.
GX-series EtherCAT Slave Unit User's Manual