Omron GX-ID1611 User Manual page 202

Gx-series, ethercat remote i/o terminal ethercat slave units
Table of Contents

Advertisement

8 Analog I/O Slave Unit
 Terminal arrangement diagram
V1
I1
+
+
1
NC
No.
(1)
Communications connectors
(2)
Unit power supply connector
(3)
Status indicators
(4)
Node Address setting Switches
(5)
Output range setting Switches
(6)
Terminal block
(7)
DIN track mounting hook
• Output range setting switches
Set output range by combination of individual DIP switches.
To enable settings of these switches, it is necessary to turn Pin8 (output range setting method) ON
in advance.
Pin No.
1
2
3
4
5
6
7
8
Precautions for Correct Use
• Pin7 must be used in the OFF state.
• To set a range using these switches, make sure to turn Pin8 ON. If it is turned OFF, the DIP
switch settings will not be reflected.
• The settings of this switch are read only once when the power is turned ON.
8 - 24
V2
I2
NC
NC
+
+
2
NC
NC
NC
NC
Name
Refer to "Specifications of Common Areas" in Page 6 - 4.
DIP switches for setting output range (Refer to the following
section.)
Terminal block for analog output signals
Fixes a Slave Unit to a DIN track.
Setting
Setting of output CH1 range
Setting of output CH2 range
Always OFF
Output range setting method
NC
NC
NC
NC
NC
V1+, V2+: Voltage output positive terminals
I1+, I2+: Current output positive terminals
1−, 2−: Voltage/current output negative terminals
NC: Not used
Set by combination of DIP switches (see the
next table)
Make sure to keep it OFF.
The operation cannot be guaranteed when it is
set to ON.
OFF: Setting by SDO communications
ON: Setting by
GX-series EtherCAT Slave Unit User's Manual
Function
Specification
these switches
(Pin1 to Pin6)