Wiring check

Confirm the wiring between remote I/O units and external equipment.
Example of wiring check
The figure below shows an example in which the head I/O No. in the FX
Y020 and 4-point mode is selected.
PLC main
unit
Operating procedure
1) Connect the FX
Set the transmission speed, point mode, station No., etc. using the DIP switches in the
FX
-64CL-M and remote I/O units.
2N
At this time, select the CONFIG mode in the FX
bit 7 OFF).
2) Supply power to the power adapter before the PLC unit.
3) When the acquisition of remote I/O unit information is completed in the CONFIG mode (that
is, when b4 of the BFM #28 (1Ch) turns ON), turn the power OFF.
4) Set the FX
to the power adapter before the FX
a) Checking the wiring between the input unit and external equipment
- Turn ON the switch corresponding to "X020" of the external equipment connected to
the input unit with station No. is 1.
- Monitor X020 from peripheral equipment.
- If X020 is ON, connection between the input unit and external equipment is normal.
b) Check the wiring between the output unit and external equipment
- Turn Y020 ON/OFF from peripheral equipment using the forced ON/OFF operation.
- If the connection between the output unit and external equipment is normal, a lamp
corresponding to "Y020" in the external equipment will light.
FX
-64CL-M
2N
(X020/Y020, 4-point mode)
Terminating
resistor
adapter
-64CL-M, power adapter and remote I/O units using the dedicated cables.
2N
-64CL-M to ONLINE mode (by setting bit 6 OFF and bit 7 OFF). Supply power
2N
Connection of Cables, Connectors and Terminating Resistors 6
4-point input unit
CL1X4-D1B2
(station No. = 1,
number of occupied
Power
stations = 1)
X020
ON
-64CL-M (by setting bit 6 ON and setting
2N
-64CL-M. Then, execute step a) or b) below.
2N
-64CL-M is X020/
2N
Terminating
resistor
4-point output unit
CL1Y4-T1B2
(station No. = 2,
number of occupied
stations = 1)
Y020
ON
6-5