Reserved Station Setting Method - Mitsubishi Electric MELSEC FX2N-64CL-M User Manual

Cc-link/lt master block
Hide thumbs Also See for MELSEC FX2N-64CL-M:
Table of Contents

Advertisement

FX2N-64CL-M CC-Link/LT Master Block
8.4.1

Reserved station setting method

Set reserved stations using the steps 1) to 4) below.
1) Set the FX
setting bit 7 to OFF). Power up the FX
(The FX
2N
2) Write the information (station type and number of I/O points) for the station to be added in
the detailed remote station information buffers [BFM #32 (20h) to #95 (5Fh)]. Set the
reserved station flag (bit 15) to ON in the appropriate BFM.
(If the bit for reserved station is set to OFF, errors such as wire breakage are detected while
a remote station is not connected.)
3) Give the instruction to write to the EEPROM [by setting from OFF to ON b4 of the BFM #27
(1Bh)].
4) After setting reserved stations, confirm that write to the EEPROM is completed by checking
b4 of the BFM #28 (1Ch). Then, set the power of the FX
procedure (setting the bit 6 of the DIP switch to OFF), and confirm that the detailed remote
station information [BFM #32 (20h) to #95 (5Fh)] is updated.
Buffer memory No.
BFM #32(20h)
BFM #33(21h)
BFM #95(5Fh)
Configuration of detailed remote station information
Bit
b0
b1
b2
b3
b4
b5 to b7
b8
b9
b10
b11
b12
b13
b14
b15
-64CL-M to the CONFIG Mode (by setting bit 6 of the DIP switch to ON and
2N
-64CL-M will assign the I/O Nos.)
.
. .
Function
Number of I/O points
(Setting prohibited)
Input flag
Output flag
(Setting prohibited)
Head station flag
Input filter setting
Output hold/clear setting
(Setting prohibited)
Reserved station flag
-64CL-M.
2N
Description
Remote station information area for the station No.1
Remote station information area for the station No.2
Remote station information area for the station No.64
1(ON)
00001:1point
00101:5points
01101:13points
00010:2points
01010:10points
01110:14points
00111:7points
01011:11points
00100:4points
01000:8points
10000:16points
The bits above are in the order "b4, b3, b2, b1, b0".
Set these bits to 0.
Input is given.
Output is given.
Set these bits to 0.
This is the head station.
High-speed input
HOLD
Set these bits to 0.
This is specified as reserved
station.
Assignment of I/O Nos. 8
-64CL-M ON using the normal
2N
.
.
.
0(OFF)
01001: 9points
00110:6points
00011:3points
01111:15points
01100:12points
Input is not given.
Output is not given.
This is not the head station.
General-purpose input
CLEAR
This is not specified as
reserved station.
8-4

Advertisement

Table of Contents
loading