FX2N-64CL-M CC-Link/LT Master Block
2.3

Performance specifications

Item
Applicable PLC
Number of connectable master
blocks
Applicable point mode
Maximum number of link points
Number of link points per station
( ) shows the number of link
points when composite I/O
module is used.
32 stations
64 stations
Communication speed
Protocol
Network topology
Error control method
Number of connected stations
Remote station numbers
Master station connection
position
RAS function
Connection cable
Number of occupied I/O points
Current consumption inside 5V DC
24V DC power
supply
Mass (weight)
*1 When connected to an FX
main and extension units.
*2 The FX
-64CL-M draws 190mA from the 5V DC source.
2N
The total 5V consumption of all special function blocks connected to a main unit or extension unit
must not exceed the 5V source capacity of the system.
(Refer to the Hardware manual of the applicable PLC)
FX
/FX
1N
(FX
-CNV-IF is required when FX
2NC
FX
Series: Up to 4
1N
FX
Series: Up to 8
2N
FX
Series: Up to 3
2NC
4-point mode and 16-point mode (selectable by DIP switch)
Connected to FX
Connected to FX
(including I/O points in PLC in each case)
Points
2.5Mbps
625kbps
156kbps
Points
2.5Mbps
625kbps
156kbps
2.5 Mbps, 625 kbps and 156 kbps (selectable by DIP switch)
BITR method (Broadcastpolling + Interval Timed Response)
Connected at end of trunk line
Communication error detection, automatic return to system, slave station
disconnection and internal loop back diagnosis
Dedicated flat cable (0.75 mm
8 points (fixed) + Number of connected remote I/O points
190 mA (Supplied by PLC via extension connector)
Voltage
Current
consumption
Initial current
Series PLC, up to two FX
1N
Specification
/FX
Series PLC (Section 4.3)
2N
2NC
*1
*2
*2
4-point mode
Series PLC: 128 points
1N
/FX
Series PLC: 256 points
2N
2NC
4 points (8 points)
128 points
0.7ms
2.2ms
8.0ms
256 points
1.2ms
4.3ms
15.6ms
64 stations maximum
2
20.4V to 28.8V DC
25 mA
35 mA
0.15 kg (0.33 lbs)
-64CL-M can be connected to each of the
2N
Series PLC is connected.)
2NC
16-point mode
16 points (32 points)
256 points
1.0ms
3.8ms
14.1ms
256 points
2.0ms
7.4ms
27.8ms
T-branch
CRC
1 to 64
× 4)
Supplied from power adapter via
connector for flat cable dedicated to
CC-Link/LT.
Specifications 2
2-3