Editing the detailed remote station information

After assigning the I/O Nos. in the CONFIG mode, the I/O No. assignment in each station No.
can be edited.
With this function, the number of I/O points can be changed, and the I/O Nos. can be assigned
to unconnected station Nos. for future use. If remote stations are added in the future, it is not
necessary to change the I/O Nos. in other remote stations and extension blocks/units
connected to the PLC.
If a remote station is not connected to an edited station No., errors such as wire breakage error
will occur.
If a remote station is connected to an edited station No. the remote station will operate with the
existing setting.
8.5.1

How to edit detailed remote station information

Edit the detailed remote station information using the steps 1) to 4) below.
1) Set the FX
setting bit 7 to OFF). Set the power of the FX
(The FX
2N
2) Write the information (station type and number of I/O points) for the station to be added in
the detailed remote station information buffers [BFM #32 (20h) to #95 (5Fh)]. Set the
reserved station flag (bit 15) to OFF in the appropriate BFM.
(If the bit for reserved station is set to ON, the station is regarded as a reserved one, and
errors such as wire breakage error cannot be detected.)
3) To the detailed remote station information on every remote station to be edited, write the
information on the remote station. Then, give the instruction for write to the EEPROM [by
setting b4 of the BFM #27 (1Bh) from OFF to ON].
4) After editing the remote station information, confirm that write to the EEPROM is completed
by checking b4 of the BFM #28 (1Ch). Then, set the power of the FX
the normal procedure (by setting bit 6 of the DIP switch to OFF), and confirm that the
detailed remote station information [BFM #32 (20h) to BFM #95 (5Fh)] is updated.
Buffer memory No.
BFM #32(20h)
BFM #33(21h)
BFM #95(5Fh)
-64CL-M to the CONFIG Mode (by setting bit 6 of the DIP switch to ON and
2N
-64CL-M will assign the I/O Nos.)
.
. .
-64CL-M to ON.
2N
Description
Remote station information area for the station No.1
Remote station information area for the station No.2
Remote station information area for the station No.64
Assignment of I/O Nos. 8
-64CL-M to ON using
2N
.
.
.
8-5

Advertisement

Table of Contents
loading

Table of Contents