Example For Writing The Operation Mode - Kollmorgen AKD PROFINET RT Communication Manual

Table of Contents

Advertisement

AKD PROFINET | 4   Installation and Setup

4.6.2 Example for writing the operation mode

For writing the operation mode an acyclic change parameter value request needs to be send
from the IO-Controller/Supervisor to the AKD.
If the user wants to write e.g. the operation mode to position mode (DRV.OPMODE 2) over
PROFINET, the PNU 930 needs to be written with value 0x0002. The PROFIdrive base para-
meter access (see "Position Units" (➜ p. 43)) describes the procedure.
Change parameter request (Operation mode):
Byte (dec) Value (hex)
The AKD answers with a positive response without values:
Byte (dec) Value (hex)
24
Kollmorgen | December 2014
Description
0
0x05
Request reference: e.g. 5
1
0x02
Request ID: Change parameters
2
0x00
Axis:  0 (the AKD parameter manager)
3
0x01
No of Parameter: 1
4
0x10
Attribute: Value
5
0x01
No. of Elements
6
0x03
PNU: 930 Operation mode
7
0xA2
8
0x00
Subindex: 0
9
0x00
10
0x42
Format: Word
11
0x01
No of Values: 1
12
0x00
Operation mode
13
0x02
Description
0
0x05
Request Ref. mirrored: e.g. 5
1
0x02
Response ID: Change parameters
2
0x00
Axis:  0 (the AKD parameter manager)
3
0x01
No of Parameter: 1
4
0x00
Format
5
0x00
No. of Values 0

Advertisement