82
en | Approved applications
19

Approved applications

The UL System Chart references the components that are evaluated and listed by UL for
compatibility with B6512/B5512/B4512/B3512. These components meet the basic system
requirements for the applicable standard.
Refer to Compatible UL listed components, page 87.
The system wiring diagrams show the relationship between the control panel and the
accessory components.
Refer to System wiring diagrams, page 73.
19.1

Optional compatible equipment

You can use UL Listed components not requiring evaluation for electrical compatibility in many
applications when installed according to the manufacturer's instructions.
19.1.1

Burglar applications

You can use UL Listed components not requiring evaluation for electrical compatibility in
burglary applications. In some cases, you must use a UL Listed interface module with the
sensors. Consult the individual component specification and installation documents to
determine suitability.
19.1.2

Bank safe and vault applications

You must use the D8108A Attack-Resistant Enclosure to meet UL Standard 681.
Refer to Rothenbuhler 5110/4001-42 High Security Bell overview, page 83 for wiring
instructions and diagrams.
Control panel enclosure requirements
UL Standard 681 for Installation and Classification of Mercantile and Bank Burglary Alarm
Systems requires foil lining or equivalent protection of the control unit enclosure. The D8108A
Attack-Resistant Enclosure does not have a foil lining, but acceptable protection is provided by
mounting electronic vibration sensors inside the enclosure.
Notice!
Proximity alarms
Do not use proximity alarms (capacitance) to protect the control panel enclosure.
Caution!
EVD installation
!
Do not install the EVD sensor within 6.4 mm (0.25 in) of the components or traces of the
printed circuit assembly.
Battery connections
2018.07 | 16 | F.01U.287.180
Install the same electronic vibration sensors in the D8108A that are used to protect the
safe or vault.
Mount the Sentrol 5402, Potter EVD-S, or Arrowhead S-3810 electronic vibration
detection (EVD) system inside the D8108A to meet the UL 681 requirements.
Install and test the EVD sensor according to the manufacturer's instructions.
Mount the EVD sensor directly inside the metal cabinet of the D8108A.
Using a D122 Dual Battery Harness, connect two 12 V 7 Ah batteries in the control panel
enclosure.
Installation Manual