Hydraulic scheme no. 7 - diagram "A" with heat buffer with layered charging buffer
1 – controller
3 – fireplace
4 – heat buffer
5 – automatic boiler
OUT-A – boiler pump
OUT-B – fireplace pump
OUT-D – diverter valve (optional)
S-P – solar pump
H1-P – direct heating circuit pump
PROPOSED SETTINGS:
Parameter
Hydraulic diagram
Pump start temperature
Pump stop temperature
Mode
Off by no heat demand
Selection
Pump start temperature
Description: After heating the sensor H4-S temperature (55C) shall be attached to the pump (OUT-B). Pump (OUT-B)
operates only when the temperature H4-S is greater than the temperature of H1-S. Pump H1-P, H2-P, H3-P will turn on
when the temperature H4-S reaches 50C and turn off when the temperature H1-S falls below 25C. Boiler (5) turns on
when the temperature measured on the sensor H1-S is below the preset
electrical voltage when the temperature measured on the sensor H5-S falling below 55C (loading upper buffer). A valve
actuator (6) is turned off when the temperature measured at the sensor H5-S rises above 55C (loading throughout the
volume of buffer). H5-S sensor activates an alarm if the exhaust temperature exceeds a critical value.
7
Shown hydraulic diagram does not replace a central heating system and can be used only for demonstrative purposes
H2-P,H3-P – adjustable heating circuit pump
H2-M, H3-M – valve electrical servo of adjustable circuit
C-P – DHW circulation pump
H1-S – upper temperature sensor buffer
H5-S – center sensor buffer
SH - solar collector temperature sensor
SL – lower solar sensor
WS - weather sensor
DHW – DHW tank temperature sensor (optional).
Setting
7
menu→ service setting → System
50C
menu→ service setting → System→ Main heat source
26C
menu→ service setting → System→ Main heat source
menu→ service setting → System→ Main heat source
ON
YES
menu→ service setting → System→ Main heat source
ON
menu→ service setting →System→ Additional heat source
55C
menu→ service setting →System→ Additional heat source
25
MENU
temperature.
On the valve actuator (6) is given an
7
:
!