Weather Control; Thermostat Settings - Salus Multi-Mix Operation And Installation Manual

Weather controller
Table of Contents

Advertisement

to this the boiler will not heat up the DHW
tank. Similar effect can be obtained by setting
the work mode for DHW tank to Off manually.
Loading DHW tank can be also optimized by
setting a lowest possible preset temperature
of DHW tank. The lower preset temperature of
HUW tank, the less often boiler will become
active in order to load the tank and solar
energy gain will be higher.
Installer from a service level should set the
highest
possible
temperature. This will generate the maximum
heat gain. On the other hand there is a risk of
scalding
with
hot
temperature limit for a particular DHW tank!
Risk of scalding with DHW!
In
order
scalding,
protective
thermostatic mixing valve.
During periods of very high insolation, there
can be a situation in which the HUW tank is
not able to absorb big amount of heat. In such
case, a solar pump transporting heat from a
solar panel to HUW tank becomes off. Due to
a risk of damaging the pump, it is turned off
only when the solar panel temperature drops.
In practice, the solar system is turned on
again the next day after the sunrise. It
indicates a normal operation resulting from
the fact that there is no possibility of
absorbing the heat surplus.

Weather control

In order for the room temperature to be
stable, must be set the weather control. The
weather control must be activated separately
for each heating circuit. The weather control
is influenced by the setting of the heating
curve and the curve parallel shift.
The heating circuit water preset temperature
is calculated basing on the temperature
prevailing outside the building. The colder it is
outside, the higher water temperature in the
heating circuit is. This relation is shown in the
controller in the form of heating curve.
The heating curve can be changed in a graph
from the system menu, within the range for
the weather preset temperature. It is a
reflection of the thermal characteristics of the
DHW
tank
maximum
water
and
exceeding
to
protect
against
install
an
additional
automatics,
building. If the building is less insulated then
the heating curve should be greater.
Setting the heating curve: Tp – temperature preset by
weather, Tz – exterlan temperature.
Heating
experimentally by changing it in a few day
intervals.
e.g.
After choosing the proper heating curve, the
circuit
preset
according to the outside temperature. As a
result if the heating curve is appropriate for
the building, the room temperature remains
constant
outside.
Guidelines for selecting a proper heating
curve:
- if at dropping external temperature, room
temperature increases, the selected heating
curve is too high,
- if at dropping external temperature, room
temperature also drops, the selected heating
curve is too low,
Poorly
warmed
higher heating curves. Whereas for well
heating buildings, heating curve will have a
smaller value.
The range of the heating curve is limited by
the minimum and maximum preset water
temperature.
In order for the room temperature to be
stable, the thermostat should be activated.
The thermostat complements the weather
17
curve
should
During trial and error selection of
appropriate heating curve, it is
necessary to exclude influence of
the
thermostat
operation (regardless of whether
the thermostat is connected or
not), by setting the parameter
Thermostat = OFF for each heating
circuit.
temperature
regardless
of
the
buildings
require

Thermostat settings

be
selected
on
regulator
is
calculated
temperature
setting