Salus Multi-Mix Operation And Installation Manual page 22

Weather controller
Table of Contents

Advertisement

Hydraulic scheme no. 4 - diagram "B" with heat buffer
1 – boiler
2 – boiler pump
3 – buffer temperature sensor
4 – heat buffer
5 – fireplace pump controlled by fireplace regulator
6 – temperaturę sensor
PROPOSED SETTINGS:
Parameter
Hydraulic diagram
Selection
Temperature
deactivating
heat source
Pump start temperature
Cooling temperature
Minimum temperature
Description: Pump (2) works together with boiler (1). When boiler (1) switches off, pump (2) deactivates with 5 minute
delay. After fireplace sensor (6) is heated up to a temperature of (35C), boiler (1) and pump (2) deactivates with 5
minute delay. Pump (5) is controlled by fireplace regulator (11). When (6) exceeds 92C, heat excess will be transferred
to heat and HUW circuits. Pump (9) will switch off if temperature on sensor (3) drops below 25C.
4
Shown hydraulic diagram does not replace a central heating system and can be used only for demonstrative purposes
Setting
4
menu→ service settings→System
menu→ service settings →System→Additional heat source
ON
main
35C
menu→ service settings →System→Additional heat source
55C
menu→ service settings →System→Additional heat source
92C
menu→ service settings →System→Additional heat source
25C
menu→ service settings → System→ Main heat source
4
:
7 – fireplace with water jacket
8 – regulated circuit water temperature sensor (H2)
9 – circuit pump (H2)
10 – electrical servo of H2 regulated heat circuit
11 – fireplace regulator
12 – thermostatic valve protecting return temperature.