H1 circuit settings – direct, unregulated
Name
Mode
Control method
Weather-set
temperature
Heat curve
Curve parallel
shift
Thermostat
Preset water
temperature
Reduce constant
water temperature
Reduce water temp.
by thermostat
Pump lock by
thermostat
Circuit name
Note: H1 circuit is a nonadjustable circuit. Due to this the H1 circuit preset temperature
is the same as the heating source preset temperature. Therefore settings concerning
heat source have a direct effect in H1 circuit. The nonadjustable H1 circuit preset
temperature will be automatically increased in order to guarantee heat for H2 and H3
adjustable circuits.
Range
Settings
ON (radiators),
ON
OFF
(radiators)
Constant value,
Weather
Weather control
control
The graph
depends on four
external
temperatures
0°C
-20...20
NO,YES
YES
45°C
20...85
0...80
10°C
0...80
10°C
NO, YES
YES
A...Z
H1
ON – enables operation of the circuit,
OFF – disables operation of the circuit, then all parameters
related to this circuit are invisible and inactive.
Constant value – constant preset temperature of water in
nonadjustable circuit is maintained.
Weather control – water preset temperature of water in the circuit
is set with consideration to external temperature sensor readings.
Parameter is invisible if no external temperature sensor is
connected. When the weather temperature sensor is defective or
not connected, the setting of the Control method is permanently
changed to Constant value.
Settings related to weather control.
Selection in the form of a heating curve graph on which the set
temperature of the heating circuit for four intermediate weather
temperatures is set: 10°C, 0°C, -10°C and -20°C.
To set the preset temperature, touch the corresponding point and
move it up or down. The higher heating temperature, the higher
temperature of water in the heating circuit. Parameter becomes
available when Control method = Weather control. Detailed
description can be found in point 10.4
Parameter enables to readjust the heating curve. Parameter
becomes available when Control method = Weather control.
Parameter assigns a thermostat to the heating circuit.
OFF – room temperature has no effect on the heating circuit,
ON – the thermostat has an effect on the preset water
temperature in the heating circuit, reducing it or completely
switching off the heating circuit.
When Control method = Constant value, heat source is disabled
when Preset water temperature is reached. Source is enabled
again after the temperature drops by heat source Hysteresis
value. Parameter is not available if Control method = Weather
control.
When Control method = Constant value, then a constant preset
temperature of water in the circuit is decreased for regulation
modes: NIGHT, AUTO.
The parameter is applicable only when Thermostat = ON.
Exceeding a room preset temperature causes a decrease of
preset temperature of water in the heating circuit Reduce water
temp. by thermostat.
Decreasing the preset temperature takes place at the moment of
opening thermostat contact. The preset temperature of the water
in the heating circuit is not changed when the Reduce water
temp. by thermostat = 0. The parameter disappears when the
Thermostat = OFF.
NO – the thermostat has no effect on the circuit operation,
YES – the circuit will be switched off when the temperature preset
on the thermostat is reached.
Enables changing name H1 circuit.