Salus Multi-Mix Operation And Installation Manual page 24

Weather controller
Table of Contents

Advertisement

Hydraulic scheme no. 6 - diagram with pelet boiler
1 – boiler
2 – solar collector temperature sensor
3 – temperature sensor for direct circuit
4 – DHW tank lower temperature sensor (lower solar
sensor)
5 – direct heating circuit pump (H1)
6 – adjustable heating circuit pump (H2)
7 – valve electrical servo of adjustable circuit (H2)
8 – water temperature sensor of adjustable circuit (H2)
9 – valve electrical servo of adjustable circuit (H3)
10 – adjustable heating circuit pump (H3)
PROPOSED SETTINGS:
Parameter
Hydraulic diagram
Pump start temperature
Minimum temperature
Hysteresis
Selection
6
Shown hydraulic diagram does not replace a central heating system and can be used only for demonstrative purposes
6
:
11 – water temperature sensor of adjustable circuit (H3)
12 – controller
13 – weather sensor
14 – DHW pump
15 – DHW tank water temperature sensor
16 – DHW circulating pump
17 – solar pump
18 – solar panel
20 – mechanical protective thermostat for protecting floor
circuit against excessive water temperature
Setting
6
menu→ service setting → System
55C
menu→ service setting → System
60C
menu→ service setting → System→ Main heat source
5C
menu→ service setting → System→ Main heat source
ON
menu→ service setting → System→ Main heat source
24
.