Huawei UPS2000-G-2KRTL User Manual page 72

Ups2000-g series
Hide thumbs Also See for UPS2000-G-2KRTL:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual
Item
Rated output voltage
Output voltage tolerance
Output frequency range
Total distortion of output voltage
waveform (THDv)
Crest factor
Inverter overload capability
Dynamic voltage tolerance ± 5%
Average frequency tracking rate
Transfer time
Issue 08 (2017-08-04)
1 kVA
200 V AC/208 V AC/220 V AC/230 V AC/240 V
AC
± 1%
A maximum of 3:1
± 5%
1 Hz/s
Transferring
0
from normal
mode to battery
mode
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 kVA
In normal mode, the UPS output frequency is
consistent with the input frequency, which is 50
Hz or 60 Hz with the tolerance of ± 3 Hz.
In battery mode, the frequency is 50 Hz or 60 Hz
(tolerance ± 0.05%).
< 6% (non-resistive load)
< 3% (resistive load)
When the ambient temperature is 0–35° C:
105%–110%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 10 minutes.
110%–130%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 1 minutes.
130%–150%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 3 seconds.
> 150%: The UPS automatically shuts down
(in battery mode) or transfers to bypass mode
(in line mode) after 0.5 seconds max.
When the ambient temperature is 35–40° C:
105%–110%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 5 minutes.
110%–130%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 30 seconds.
130%–150%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 1.5 seconds.
> 150%: The UPS automatically shuts down
(in battery mode) or transfers to bypass mode
(in line mode) after 0.5 seconds max.