UPS2000-G-(1 kVA-3 kVA)
User Manual
Alar
Alar
Alar
m ID
m
m
Cause
Name
ID
l fault
42
28
Interna
l fault
Interna
42
31
l fault
Issue 08 (2017-08-04)
Alarm
Alarm Clear
Severity
Mode
must be
manually
cleared.
Critical
The first three
alarms are
cleared
automatically
in 10 minutes.
Later alarms,
if generated,
must be
cleared
manually.
This alarm
Critical
must be
manually
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
output
is generated
voltage is
during the
lower than
running of
75% of the
the UPS, the
rated output
UPS
voltage, and
transfers to
the output
bypass
current is
mode.
lower than
60% of the
rated output
current.
The inverter
If this alarm
output
is generated
voltage is
during the
lower than
running of
100 V.
the UPS, the
UPS
transfers to
no output.
After 10
minutes, the
UPS
automaticall
y starts the
inverter. If
this alarm
persists, the
UPS then
transfers to
no output
again. After
the UPS
transfers to
no output
three times,
the alarm
needs to be
manually
cleared.
The
If this alarm
difference
is generated
between the
during the
4 Setting Control Panel
Repair Proposal
Possible cause:
The output load
types are not
supported or the
load exceeds the
specifications.
Measure: Check
whether the load
types are
supported and
reduce the
output load.
Then, manually
clear the alarm
and restart the
UPS.
Possible cause:
The inverter is
faulty.
Measure:
Contact the
dealer or
Huawei
technical
support.
Possible cause:
The output is
short-circuited.
Measure: Check
whether the
output is
short-circuited.
Possible cause:
The hardware is
damaged.
43