UPS2000-G-(1 kVA-3 kVA)
User Manual
Alar
Alar
Alar
m ID
m
m
Cause
Name
ID
42
18
Interna
l fault
42
24
Interna
l fault
42
27
Interna
l fault
Interna Critical
Issue 08 (2017-08-04)
Alarm
Alarm Clear
Severity
Mode
Critical
This alarm
must be
manually
cleared.
Minor
This alarm is
automatically
cleared.
Critical
This alarm
must be
manually
cleared.
This alarm
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The bus
If this alarm
voltage is
is generated
lower than
during the
260 V.
running of
the UPS, the
UPS
transfers to
bypass
mode.
An error
All UPS
occurs in the
parameters
EEPROM.
are restored
to the
factory
settings. If
this alarm is
generated,
the customer
needs to
replace the
UPS.
The inverter
If this alarm
voltage is
is generated
higher than
during the
1.15 times the
running of
rated output
the UPS, the
voltage.
UPS
transfers to
bypass
mode.
The inverter
If this alarm
4 Setting Control Panel
Repair Proposal
damaged.
Measure:
Contact the
dealer or
Huawei
technical
support.
Possible cause:
The hardware is
damaged.
Measure:
Contact the
dealer or
technical
support.
Possible cause:
An overload
occurred when
the input voltage
was low.
Measure:
Rectify the fault
and restart the
UPS.
Possible cause: The
EEPROM is faulty.
Measure: Contact
the dealer or
Huawei technical
support.
Possible cause: The
inverter is faulty.
Measure: Contact
the dealer or
Huawei technical
support.
42