Huawei UPS2000-G-2KRTL User Manual page 52

Ups2000-g series
Hide thumbs Also See for UPS2000-G-2KRTL:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual
Alar
Alar
Alar
m ID
m
m
Cause
Name
ID
Interna
42
42
l fault
66
1
Output
overlo
ad
66
2
Output
overlo
ad
66
3
Output
overlo
ad
Issue 08 (2017-08-04)
Alarm
Alarm Clear
Severity
Mode
cleared.
This alarm
Critical
must be
manually
cleared.
Minor
This alarm is
automatically
cleared.
Minor
This alarm is
automatically
cleared.
Critical
This alarm
must be
manually
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
the UPS is
not affected.
The voltage
The UPS
of each
transfers to
battery
bypass
decreases to
mode.
below 10 V
when the
charger has
no output and
the UPS
inverter is
started.
The inverter
The power
output load is
supply from
more than
the UPS is
105% of the
not affected.
rated load.
The bypass
The power
output load is
supply from
more than
the UPS is
110% of the
not affected.
rated load.
In battery
For
mode, this
battery
alarm is
mode,
generated
the UPS
when the
transfers
load
to no
exceeds
output
the rated
mode.
load.
If the
In normal
UPS
4 Setting Control Panel
Repair Proposal
of the charger is
abnormal. Measure:
Contact the dealer
or Huawei technical
support.
Possible cause: The
charger switching
transistor is faulty.
Measure: Contact
the dealer or
Huawei technical
support.
Possible cause: The
load exceeds the
rated loading
capacity of the
inverter.
Measure: Lower the
load or replace the
UPS with a UPS
with a larger
capacity.
Possible cause: The
load exceeds the
rated loading
capacity of the
bypass.
Measure: Lower the
load or replace the
UPS with a UPS
with a larger
capacity.
Possible cause: The
load exceeds the
rated loading
capacity of the
inverter.
Measure: Lower the
load or replace the
UPS with a UPS
with a larger
capacity.