UPS2000-G-(1 kVA-3 kVA)
User Manual
Alar
Alar
Alar
m ID
m
m
Cause
Name
ID
30
1
Interna
l
overte
mperat
ure
Interna
42
15
l fault
Interna
42
17
l fault
Issue 08 (2017-08-04)
Alarm
Alarm Clear
Severity
Mode
Minor
This alarm is
automatically
cleared.
This alarm
Critical
must be
manually
cleared.
This alarm
Critical
must be
manually
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The ambient
The UPS
temperature
remains in
exceeds 50º C.
the current
state and
cannot start.
The bus
This alarm is
voltage is
generated
lower than
during the
320 V.
startup of
the UPS. If
this alarm is
generated,
the UPS
fails to start.
The bus
If this alarm
voltage is
is generated
higher than
during the
450 V.
running of
the UPS, the
UPS
transfers to
bypass
mode.
4 Setting Control Panel
Repair Proposal
replace batteries.
Possible cause: The
ambient
temperature
exceeds 50º C when
the UPS is in
standby mode. As a
result, the UPS
cannot start.
Measure: Lower the
ambient
temperature at
which the UPS
works.
Possible cause: The
soft-start resistor is
damaged.
Measure: Contact
the dealer or
Huawei technical
support for repair.
Possible cause:
The mains has
experienced a
transient high
voltage.
Measure:
Rectify the fault
and restart the
UPS.
Possible cause:
The output
supplies power
to special loads
such as the
inductive and
rectification
loads.
Measure: Check
that the load
types are
supported by the
UPS.
Possible cause:
The hardware is
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents