Huawei UPS2000-G-2KRTL User Manual page 47

Ups2000-g series
Hide thumbs Also See for UPS2000-G-2KRTL:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual
Alar
Alar
Alar
m ID
m
m
Cause
Name
ID
29
1
Batter
y
requiri
ng
mainte
nance
Issue 08 (2017-08-04)
Alarm
Alarm Clear
Severity
Mode
This alarm is
Minor
automatically
cleared.
Minor
This alarm is
automatically
cleared.
Minor
This alarm is
automatically
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
the UPS
fails to
start.
If battery
packs are
connecte
d during
the
running
of the
UPS, the
UPS
transfers
to bypass
mode.
For standrd
The power
model, the
supply from
voltage of
the UPS is
each battery
not affected.
is lower than
11.28 V. For
long backup
time model,
the voltage of
each battery
is lower than
10.9 V.
The battery
The power
voltage is
supply from
lower than
the UPS is
the battery
not affected.
replacement
voltage (11
V) when
batteries are
in self-check
mode.
The voltage
The UPS
of each
remains in
battery is
the current
lower than 5
state and
V, or is
cannot start.
higher than
15 V (when
the UPS is
not started).
4 Setting Control Panel
Repair Proposal
Measure:
Connect to the
mains in
non-battery test
state.
Possible cause:
The actual
number of
batteries does
not meet
requirements.
Measure: Check
that the actual
number of
batteries meets
requirements.
Possible cause:
The battery is
damaged.
Measure:
Contact the
dealer or
Huawei
technical
support to
40