UPS2000-G-(1 kVA-3 kVA)
User Manual
Alar
Alar
Alar
m ID
m
m
Cause
Name
ID
66
4
Output
overlo
ad
Issue 08 (2017-08-04)
Alarm
Alarm Clear
Severity
Mode
Critical
This alarm
must be
manually
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
mode,
transfers
when the
from
bypass
normal
input is
mode to
normal,
bypass
this alarm
mode
is
three
generated
times
when the
within 20
UPS
minutes,
transfers
the UPS
to normal
is locked
mode
in bypass
three
mode.
times
For
within 20
normal
minutes
mode,
after the
the UPS
UPS
transfers
transfers
to no
from
output
normal
mode.
mode to
bypass
mode.
In normal
mode,
when the
bypass
input is
abnormal,
this alarm
is
generated
when the
UPS
transfers
to no
output
mode.
The bypass
The UPS
overload
transfers to
exceeds the
no output.
time limit.
4 Setting Control Panel
Repair Proposal
Possible cause: The
load exceeds the
rated load of the
bypass.
Measure: Reduce
the load or replace
the UPS with a UPS
with a larger
46