UPS2000-G-(1 kVA-3 kVA)
User Manual
Alar
Alar
Alar
m ID
m
m
Cause
Name
ID
22
1
Batter
y
discon
nected
25
1
Batter
y
overvo
ltage
Issue 08 (2017-08-04)
Alarm
Alarm Clear
Severity
Mode
Minor
This alarm is
automatically
cleared.
Minor
This alarm is
automatically
cleared.
Critical
This alarm
must be
manually
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
Discharge
The UPS
ends for the
fails to start.
UPS in
battery mode,
or the battery
voltage is
lower than
the minimum
startup
voltage
(11.28 V) for
the UPS in
normal mode.
Batteries are
The power
not
supply from
connected,
the UPS is
connected
not affected.
improperly,
or damaged.
The voltage
This alarm is
of each
generated
battery
because
exceeds 15 V
there are
(when the
more
UPS is
batteries
started).
than
required.
The impact
is as
follows:
If battery
packs are
connecte
d before
the
startup,
the UPS
4 Setting Control Panel
Repair Proposal
Possible cause: The
battery voltage is
low or the batteries
are damaged after
EOD.
Measure: Wait for
the batteries to
recover or contact
the battery supplier
to replace the
batteries.
Possible cause:
No batteries are
connected.
Measure:
Connect
batteries.
Possible cause:
The batteries are
in poor contact.
Measure: Check
the battery cable
connection. If
battery cables
are loose,
connect them
securely.
Possible cause:
The actual
number of
batteries does
not meet
requirements.
Measure: Check
that the actual
number of
batteries meets
requirements.
Possible cause:
The charger is
abnormal.
Measure: Check
that the charger
voltage is
normal
38