Huawei UPS2000-G-2KRTL User Manual page 44

Ups2000-g series
Hide thumbs Also See for UPS2000-G-2KRTL:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual
Alar
Alar
Alar
m ID
m
m
Cause
Name
ID
10
1
Bypas
s
voltag
e
abnor
mal
2
Bypas
s
freque
ncy
abnor
mal
14
1
Startu
p
timeou
t
Issue 08 (2017-08-04)
Alarm
Alarm Clear
Severity
Mode
Minor
This alarm is
automatically
cleared.
Minor
This alarm is
automatically
cleared.
Critical
This alarm
must be
manually
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The bypass
The UPS
voltage is
remains in
outside the
the current
scope.
state. If the
UPS works
in bypass
mode, it
transfers to
standby
mode and
has no
output.
The bypass
The UPS
frequency is
remains in
outside the
the current
bypass
state. If the
frequency
UPS works
range.
in bypass
mode, it
transfers to
standby
mode and
has no
output.
The inverter
If this alarm
output
is generated
voltage is not
during the
within ± 2 V
running of
of the rated
the UPS, the
output.
UPS
transfers to
bypass
mode.
4 Setting Control Panel
Repair Proposal
Possible cause: The
bypass input
voltage is abnormal.
Measure: Check
whether the bypass
input voltage
exceeds the
configured range. If
yes, change the
range or wait until
the bypass input
recovers.
Possible cause: The
bypass input
frequency is
abnormal.
Measure: Check
whether the bypass
input frequency
exceeds the
configured range. If
yes, change the
range or wait until
the bypass input
recovers.
Possible cause:
The bypass
loading capacity
exceeds the
rated load of the
inverter.
Measure:
Reduce the
output load,
manually clear
the alarm, and
restart the UPS.
Possible cause:
An internal fault
has occurred.
Measure:
Contact the
dealer or
Huawei
technical
support.
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents