Huawei UPS2000-G-2KRTL User Manual page 29

Ups2000-g series
Hide thumbs Also See for UPS2000-G-2KRTL:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual
No.
3
4
5
6
7
Issue 08 (2017-08-04)
Item
Cable connections for
USB ports and network
ports
Cable labels
Ground cable
connection
Distances between cable
ties
Operating environment
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Acceptance Criterion
Cables to USB ports and network ports are connected
correctly and securely.
Labels are neatly attached to both ends of each cable,
and the information on the labels is concise and
understandable.
The ground cable is securely connected to the
equipment room ground bar. Measure the resistance
between the UPS ground cable and the equipment room
ground bar, which must be less than 1 ohm.
Distances between cable ties are the same, and no burr
exists.
Clean the conductive air and other sundries.
3 Installing the UPS