UPS2000-G-(1 kVA-3 kVA)
User Manual
Display
The highest input voltage in bypass mode should be higher than the highest input voltage in ECO mode.
Display
The lowest input voltage in bypass mode should be lower than the lowest input voltage in ECO mode.
Display
Display
Issue 08 (2017-08-04)
Set the lowest input voltage in bypass mode.
Set the battery capacity.
Set the discharge time limit.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Setting Control Panel
Setting
Press ▼ or ▲ to adjust and set the highest
input voltage in bypass mode.
230–264: The value range is 230 V AC to
264 V AC, and the default value is 264 V
AC.
Setting
Press ▼ or ▲ to adjust and set the lowest
input voltage in bypass mode.
170–220: The value range is 170 V AC to
220 V AC, and the default value is 170 V
AC.
Setting
Press ▼ or ▲ to adjust and set the UPS
battery capacity.
18–999: Set the UPS battery capacity in the
range of 18 Ah to 999 Ah. (The default
value for standard model is 9 Ah and not
configurable. The default value for long
backup time model is 18 Ah.)