Figure 5-1 Power-on and standby screen
Step 2 Set the voltage level based on the actual output voltage. The voltage level can be set to 200 V,
208 V, 220 V, 230 V (default), or 240 V.
Figure 5-2 Setting the output voltage
Step 3 Set the system output frequency based on the rated frequency. The values include 50 Hz, 60
Hz, and AUT (default).
Figure 5-3 Setting the system output frequency
Step 4 (This step is required only for the UPS with long backup time.) Set the battery capacity to the
total capacity of all batteries actually connected. The default value is 18 Ah for the UPS with
long backup time, and the value can range from 18 Ah to 999 Ah.
Figure 5-4 Setting the battery capacity
Step 5 Start the UPS to inverter mode.
Issue 08 (2017-08-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations