Huawei UPS2000-G-2KRTL User Manual page 51

Ups2000-g series
Hide thumbs Also See for UPS2000-G-2KRTL:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual
Alar
Alar
Alar
m ID
m
m
Cause
Name
ID
42
32
Interna
l fault
42
36
Interna
l fault
Issue 08 (2017-08-04)
Alarm
Alarm Clear
Severity
Mode
cleared.
Critical
This alarm
must be
manually
cleared.
Minor
This alarm is
automatically
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
absolute
running of
value of the
the UPS, the
positive bus
UPS
voltage and
transfers to
that of the
bypass
negative bus
mode.
voltage is 100
V.
The ambient
The UPS
temperature
transfers to
exceeds 50º C
bypass
mode. When
the
temperature
decreases,
the UPS
automaticall
y starts and
clears this
alarm. If this
alarm is
generated
three times
within 3
hours, the
UPS does
not start or
clear the
fault.
The charger
The power
has no output.
supply from
4 Setting Control Panel
Repair Proposal
Measure:
Contact the
dealer or
Huawei
technical
support.
Possible cause:
The UPS
supplies power
to half-wave
loads.
Measure: Check
that the load
types are
supported by the
UPS.
Possible cause:
The ambient
temperature
exceeds 50º C.
Measure: Lower
the ambient
temperature.
Possible cause:
Air channels are
blocked.
Measure: Keep
the air intake
and exhaust
vents of the UPS
unblocked.
Possible cause:
The fan is
abnormal.
Measure: Clean
up the foreign
matter around
the fan. If the
alarm persists,
contact the
dealer or
Huawei
technical
support.
Possible cause: The
internal connection
44