CHAPTER 4 - INSTALLATION INSTRUCTIONS
The analogue output can be configured for 0 - 20mA or 4 - 20mA output
modes. Check the configuration sheet supplied with the system to
determine the factory configured operating mode. The operating mode
can be reconfigured easily using a computer attached to the Engineering
Port. Contact Zellweger Analytics or your local agent for more information.
The analogue output can be connected to voltage input device (eg.
chart recorders) by including an external sense resistor in series with
the loop and connecting the device input in parallel with the resistor. ie.
Use a 100 ohm resistor and select an input range of 2V on the chart
recorder.
Single Channel Control Card
05701-A-0301 4 - 20mA
05701-A-0302 Catalytic
+
Current
Sense
-
Non-isolated Analogue Output Connection with Power from
Fitted with Analogue Output
Module 05701-A-0285
Relay/Field Interface Card
05701-A-0326
05701-A-0327
05701-A-0328
05701-A-0329
05701-A-0330
Analogue O/P+
Analogue O/P -
System 57.
4 - 63
5701 Control System
31
32
36
35
+24V
0V