Miscellaneous Errors - Honeywell 5701 Operating Instructions Manual

Sieger system 57
Table of Contents

Advertisement

MAN0443.P65 Issue 13 Aug 04
05701-M-5001 A02279
CHAPTER 5 - COMMISSIONING AND
MAINTENANCE INSTRUCTIONS
Error
Code
64
63
62
5.6
Error
Code
07
01
Error Code Meaning
Timeout Error
Backplane command timed out.
Reset card by removing power to the
card. If problem persists, replace the
card.
Slot Inactive Error
Backplane command sent to empty slot.
Reset card by removing power to the
card. If problem persists, replace the
card.
Not applicable.
Communications Error
A participant in a complex alarm function
hosted by this card has stopped
communicating.
Check all cards within the participant
group are fully inserted into the rack and
are functioning correctly.

Miscellaneous Errors

Error Code Meaning
Divide By Zero.
Internal calculation error.
Reset card by removing power to the
card. If problem persists, replace the
card.
Invalid Command
A serial command has been received
that is not valid for this card.
5 - 18
5701 Control System
S/W
Card
Fault
Status Signal
All
Active
No
All
Active
No
1Vx
-
-
-
2Vx
Active
Yes
S/W
Card
Fault
Status Signal
All
Active
No
All
Active
No
Latch
No
No
-
-
No
Latch
No
No