Analogue Output Module; Engineering Card - Honeywell 5701 Operating Instructions Manual

Sieger system 57
Table of Contents

Advertisement

MAN0443.P65 Issue 13 Aug 04
05701-M-5001 A02279
CHAPTER 8 - SPECIFICATION
Measurement Signal Range:
Maximum Line Resistance: 500 ohms loop resistance including
Isolation Breakdown
Voltage:
5.5

Analogue Output Module

Output Compliance Range: 40V.
Protection:
Configuration:
Signal Range:
Measurement Signal Range: 0 - 20mA or 4 - 20mA selected by the
Linearity From Input:
Repeatability From Input:
Note: The repeatability performance derating is a consequence of the
direct injection test on an installation using unscreened cable
which is part of the EMC testing to Industrial Standards
EN50270:1999.
Isolation Breakdown
Voltage:
5.6

Engineering Card

LEDs:
0 to 25mA.
sensor.
More than ±50V dc to system 0V.
Short circuit protected.
Reverse voltage up to 36V dc.
Transient voltage of less than 60V dc.
Isolated current sink.
Isolated current source with external supply.
0 - 25mA.
software.
Better than ±2% fsd.
Better than ±1% fsd.
Depending upon the installation, a loss of
performance of less than ±5% fsd may be
observed under extreme conditions of EMC
susceptibility.
More than ±50V dc to system 0V.
Power On (
Unlocked (
8 - 7
5701 Control System
- Green LED).
- Red LED).

Hide quick links: