CHAPTER 4 - INSTALLATION INSTRUCTIONS
Single Channel Control Card 4 - 20mA 05701-A-0301
Fitted with 4 - 20mA Sensor Drive 05701-A-0283
Searchpoint Optima
(Configured for current
sink using hybrid
module 04200-A-0145)
Earth
Terminal
Note: 1.
Where a sensor is earthed locally, either to the Earth Stud or
through the sensor casing or mounting, to avoid earth loops
the screen sheath of the cable should only be connected at
one end. ie. At the sensor or at the Interface/relay Card.
2.
The Optima analogue output is non isolated and is factory
configured as current sink or current source. The actual
configuration is identified by a label on the Optima white
4 - 20mA output lead.
Three Wire Control Card Current Source, Transmitter Current Sink Connection for
Searchpoint Optima (Signal Returned to Regulated +23V Supply)
Junction
Box
Terminal
Block
SHC1
-
Green/Yellow - Ground
Black - 0V DC Supply
White - 4 - 20mA Output
Red - +24V Supply
Blue
Communications
Orange
Link to SHC1
Relay/Field Interface Card
05701-A-0326
05701-A-0327
05701-A-0328
05701-A-0329
05701-A-0330
Arrows Indicate
Direction of Loop
Current Flow
+24V
4 - 20mA
0V
GND
Screened
Cable
4 - 40
5701 Control System
Cabinet
S
27
01
28
NS
29
Protective
Earth
Link Positions
LK12
LK9
LK6
LK3
LK1