Disconnecting The Condensate Trap; Removing The Condensate Collector - Worcester GB162-50 Installation And Servicing Instructions

Commercial
Table of Contents

Advertisement

13.2.5 Disconnecting the condensate trap

▶ Disconnect the condensate trap hose [3] and the rubber sleeve [2]
from the condensate trap [1].
▶ Turn the trap clockwise a quarter turn.
1
Fig. 112 Disconnecting the condensate trap hose
[1]
Condensate trap
[2]
Rubber sleeve
[3]
Condensate trap hose
▶ Disconnect the condensate trap from the coupling and remove it [1].
1
Fig. 113 Disconnecting the condensate trap in the pump group
▶ Rinse the condensate trap to clean it.
▶ Fill the condensate trap with approximately 1.0 l. water before
refitting it.
The condensate trap has a bayonet connector. After
inserting it, the condensate trap must be turned
clockwise through ¼ rotation until it clicks into place
( fig. 17, page 17).
6720813171 (2015/04)

13.2.6 Removing the condensate collector

▶ Disconnect the flexible condensate drain hose and bend it
backwards.
2
3
6 720 648 726-113.1TD
Fig. 114 Removing the condensate trap hose
▶ Open the 2 clamps on the right and left at the bottom of the
condensate collector [1].
▶ Pull the condensate collector down (step 1) and remove it by pulling
it towards you (step 2).
1
6 720 648 726-114.1TD
Fig. 115 Removing the condensate collector
▶ Check the condensate collector for damage and replace it if required.
▶ Clean the condensate collector mechanically (using compressed air
or a soft brush) and rinse it with clean water.
Fig. 116 Cleaning the condensate collector
Maintenance
6 720 648 726-115.1TD
1
1
2
6 720 648 726-116.1TD
6 720 648 726-117.1TD
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gb162-80Gb162-65Gb162-100