1MRK 511 398-UEN C
8.2.2
670 series 2.2 IEC
Engineering manual
•
Knowledge of the IEC 61850 engineering process as described in the IEC
61850 standard.
•
The IEC 61850 conformance documents for the IED to be engineered.
•
The Technical reference manual describes function blocks defined as logical
nodes.
•
IEC 61850 Data objects list for the IED.
Sequence for engineering of IEC 61850 protocol
The IEC 61850 standard defines the complete part needed for information
communication in a substation. This can be split into the following parts:
•
Description of the substation part including the used logical nodes
•
Description of the IEDs with their logical nodes
•
Description of the communication network
•
Description of the engineering process
For more details please refer to the IEC 61850 standards. In the following
description it is assumed that PCM600 together with Integrated Engineering Tool
(IET600) is used as system configuration tool.
A short form of a typical sequence is shown in
is exported as a SCD file.
1.
Export SCL files from PCM600. In the scenario in
Other SCL file types are possible to export.
2.
Configure horizontal and vertical communication in the IET600 station
configuration tool.
3.
Import SCL files to PCM600 project. In the scenario in
updated SCD file.
IEC 61850 communication engineering
Figure 69
Section 8
SEMOD58549-17 v9
when a complete station
Figure 69
it is a SCD file.
Figure 69
it is the
111