Section 7
Local HMI engineering
104
•
Switch controller (of type CSWI) for an apparatus.
•
All configured function blocks with measurements (of type MMXU) for the
measurements.
•
VSGAPC for two bit indications for the dynamic text symbols.
•
SLGAPC for 32 bit indications for the dynamic text symbols.
Procedure
1.
Right-click the apparatus symbol and select Select Input Signal. A list of
engineered switch control application function blocks opens, see
2.
Select the switch control application function block that corresponds to the
selected apparatus.
3.
Right-click the measurement symbol and select Select Input Signal. A list of
the engineered measurement application function blocks opens.
4.
Select the measurement application function block that corresponds to the
selected symbol.
IEC08000125 V2 EN-US
Figure 63:
GDE: Input signal selection
The number of order in the selection window of the process objects corresponds to
the number given in the PST tree and to the application function block in ACT.
Only those apparatus and measurements are shown that are configured in the
application configuration program.
1MRK 511 398-UEN C
Figure
63.
IEC08000125-2-en.vsd
670 series 2.2 IEC
Engineering manual