1MRK 511 398-UEN C
670 series 2.2 IEC
Engineering manual
IEC09000656 V1 EN-US
Figure 49:
LHMI: Function key operation mode
The LEDs have a number of different operation modes, see
General definitions
Each LED can illuminate in one of three colors: RED, YELLOW,
GREEN.
Only one color is illuminated at a time.
The priority for illumination and the color is linked.
Prio 1 = RED
Prio 2 = YELLOW
Prio 3 = GREEN
When RED and YELLOW are ON at the same time, the LED will
illuminate in RED.
The operator's acknowledgement for the LED signals is done for all three
signals (RED, YELLOW, GREEN) of the LED.
A reset of the LEDs operates also on all three signals of the LEDs.
Follow-S
The LED illumination follows the status of the signal. The LED
illuminates steady (S).
Follow-F
The LED illumination follows the status of the signal. The LED
illuminates flashing (F).
LatchedAck-F-S
The LED latches the signal change OFF-ON and flashes (F) until it is
acknowledged.
When the signal is still ON at the time the signal is acknowledged, the
LED changes to steady (S) mode.
When the signal has already changed to OFF before the time it is
acknowledged, the LED turns to OFF.
LatchedAck-S-F
Section 7
Local HMI engineering
IEC09000656-1-en.vsd
Figure
50: