Adding Setting Groups - ABB Relion 670 series Engineering Manual

Version 2.2 iec
Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

Section 10
DNP3 communication engineering
10.2
138

Adding setting groups

In order to show for a DNP master which setting group is used, the procedure
outlines here can be performed.
In this example, only setting groups one and two are used. The DNP master will
get two binary inputs: the first is set if setting group one is used, the second is set if
setting group two is used.
1.
Configure ACTVGRP (Basic IED functions) and SP16GAPC (Monitoring)
with the Application Configuration Tool (ACT).
IEC11000423 V3 EN-US
Figure 91:
Application configuration tool
To make it easier to recognize the signals for the active setting
group, user-defined names are used.
2.
Open the Communication Management Tool (CMT). Set the Signal Type to
Binary Input Object, and choose the connection of the master for which the
values should be presented.
1MRK 511 398-UEN C
GUID-9C636C53-898E-4A60-9DDA-1DB13A65EE30 v3
ACTVGRP
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
ACTGRP4
GRP4
ACTGRP5
GRP5
ACTGRP6
GRP6
SETCHGD
REMSETEN
^IN16
ACTVGRP
SP16GAPC
BLOCK
GRP1
^IN3
GRP2
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
IEC11000423-3-en.vsd
670 series 2.2 IEC
Engineering manual