Engineering Concept In Iec 61850-6 - ABB Relion Series 670 Manual

Hide thumbs Also See for Relion Series 670:
Table of Contents

Advertisement

1MRK 511 349-UEN -
3.5
670 series 2.1 IEC
Communication protocol manual
Substation Configuration description Language (SCL)
IET600:
Open a SCD file or import/merge a SCD, ICD or CID file for the particular
IED(s).
For each IED, the user defines the datasets, the control blocks for reporting (this
means unbufffered/buffered reporting and GOOSE) and the properties for each
report control block.
Data sets (DS) are generated automatically in PCM600. Report
control blocks (RCBs) are not generated automatically in
PCM600.
If client definitions (like client. ICD) are required in the system configuration,
they are merged into IET600 and connected to the unbuffered/buffered report
control blocks.
Logical nodes, which are not related to the conducting equipment, must be
included in the bay level in the substation section.
The resulting SCD file is exported from IET600.
PCM600:
Define the inputs for the client in IET600 and cross-reference the signals in SMT.
Import the SCD file to PCM600 to receive GOOSE data. For each IED that shall
receive GOOSE information, the received data is connected to the applications using
SMT in PCM600.To be able to import scd-file to PCM600 61850 engineering in PCM
must be set to disabled.
If input signals are not defined for clients in IET600, they will not be
visible in SMT. Inputs (GOOSE clients) can also be defined in
PCM600.

Engineering concept in IEC 61850-6

Top-down approach means that the system engineering tool has ICD files
available for each IED to be included in the system configuration. The ICD files
may be of the template type and represent a pre-configured IED.
Bottom-up approach means that the configurations are produced by the IED tool,
and that are exported as CID files (or SCD file) to be imported into the system
tools.