Deleting Connections; Cut-Paste And Copy-Paste Of Act Goose Variables; Goose Online Monitoring; Engineering Of Vertical And Horizontal Communication In Iet600 - ABB Relion 670 series Engineering Manual

Version 2.2 iec
Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

Section 8
IEC 61850 communication engineering
8.4.4
8.4.5
8.4.6
8.5
126

Deleting connections

The following connections cannot be deleted in ACT:
GOOSE sending variable
Link between the GOOSE sending variable and signal
Function block to which the GOOSE sending variable is connected
MainApp/Page containing the GOOSE sending variable.

Cut-Paste and Copy-Paste of ACT GOOSE variables

The GOOSE variables alone cannot be pasted. They can be cut or pasted only with
the connected block.
Copying and pasting of GOOSE variables within the same IED is not allowed. If
the GOOSE variable is copied along with the connected block, only the block is
copied provided that the instance is available.
GOOSE variables and worksheets can be copied and pasted into other IEDs.
However, the GOOSE sending variables are not copied. The receiving GOOSE
variables are copied unless they are already present in the other IED.

GOOSE Online Monitoring

Click Work online on the toolbar in ACT for Online Monitoring for the GOOSE
sending signals and receiving signals. The sending or receiving GOOSE variable
shows the value being sent or received over GOOSE.
Engineering of vertical and horizontal
communication in IET600
For IEC 61850 engineering, a separate system configuration tool may be needed
with PCM600 (for example, when using other than ABB IEDs).
Procedure for vertical engineering using IET600:
1.
Create a project in IET600.
2.
Import the SCD file exported from PCM600.
All data sets, report control blocks and GOOSE control blocks
must be located at LD0/LLN0. There are limitations regarding
1MRK 511 398-UEN C
GUID-0D3B0D71-7077-4A39-9A33-E1E37F98324C v1
GUID-48CAD18F-99B4-41C4-BEF7-0BC389E8EC2E v1
GUID-1778C485-55D8-4DBB-B90C-16A5D5545BB3 v2
GUID-04ED1306-BAE6-49D2-8C84-11849EACC711 v9