Section 7
Local HMI engineering
7.1.2
88
•
The same as LatchedAck-F-S but the LED starts with steady state and
flashes after acknowledgment.
•
LatchedColl-S
•
The LED illuminates in all cases in steady mode only
•
The LED latches a signal change from OFF-ON until it is acknowledged
by the operator.
•
The LED stays in steady mode when it is reset and the signal is still in
ON state.
•
The LED is OFF only after the signal has changed to OFF state AND it
is reset by the operator via 'Clear' operation.
•
LatchedReset-S
•
This mode is used for all LEDs that are used to indicate a disturbance.
The LEDs will stay in the last state after the disturbance run time until
they are reset after a defined time.
•
The timers are set in the Parameter Setting tool in the function block
LEDGEN.
IEC09000657 V1 EN-US
Figure 50:
LHMI: LED operation mode
LED operation modes
The SequenceType parameter enables each LED to operate in one out of six
different modes.
•
Follow-S
•
Follow-F
•
LatchedAck-F-S
•
LatchedAck-S-F
•
LatchedColl-S
•
LatchedReset-S
1MRK 511 398-UEN C
IEC09000657-1-en.vsd
GUID-40B89A33-3C2D-488C-8932-F862E0C9F477 v4
670 series 2.2 IEC
Engineering manual