1MRK 511 398-UEN C
Section 11
11.1
11.1.1
670 series 2.2 IEC
Engineering manual
Flexible product naming

IEC 61850 Structure Mapping Tool

IEC 61850 Structure Mapping Tool is used to manage the data model of IED,
where one can change the IEDs IEC 61850 data model as per the requirement. This
can be done by mapping the data model with customer specific data model. The
IEC 61850 structure mapping tool is available only in FPN projects in PCM600. A
PCM600 project can be converted into an FPN project by importing an FPN SCD
file into it. FPN is supported for both IEC 61850 Edition 1 and IEC 61850 Edition
2.
FPN allows the use of standardized, predefined and IED-vendor independent
templates for building and maintaining substations. Refer to the PCM600 online
help for more detailed information about FPN.

User interface

1
IEC15000082 V2 EN-US
Figure 102:
Mapping Tool
1. Plant Structure
2. IEC 61850 Structure Mapping
3. Object Properties
Plant Structure
The data tree displays the Flexible Product Naming (FPN) IEDs, non-FPN IEDs
and mapped IEDs under substation; internal IEDs under unassigned IEDs.
IEC 61850 structure Mapping
Flexible product naming
GUID-079F55A1-84A7-4920-87DF-0251A08D2BD4 v2
GUID-7E8E092D-E671-4A8E-9069-237D2A62515B v2
2
Section 11
3
IEC15000082-2-en.vsdx