Section 9
IEC 60870-5-103 communication engineering
134
EvalTimeAccuracy
EventRepMode
CmdMode
RepIntermediatePos
<config-selector> is:
"OPTICAL103:1" for the optical serial channel on the SLM
"RS485103:1" for the RS485 port
2.
The protocol to activate on a physical port is selected under:
Main menu/Configuration/Communication/Station Communication/Port
configuration/
RS485 port
RS485PROT:1 (off, DNP, IEC103)
SLM optical serial port
PROTOCOL:1 (off, DNP, IEC103, SPA)
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN-US
Figure 90:
Settings for IEC 60870-5-103 communication
The general settings for IEC 60870-5-103 communication are the following:
SlaveAddress and BaudRate: Settings for slave number and communication
speed (baud rate).
The slave number can be set to any value between 1 and 254. The
communication speed, can be set either to 9600 bits/s or 19200 bits/s.
RevPolarity: Setting for inverting the light (or not). Standard IEC 60870-5-103
setting is On.
CycMeasRepTime: See I103MEAS function block for more information.
EventRepMode: Defines the mode for how events are reported. The event
buffer size is 1000 events.
Event reporting mode
If EventRepMode = SeqOfEvent, all GI and spontaneous events will be delivered in
the order they were generated by BSW. The most recent value is the latest value
delivered. All GI data from a single block will come from the same cycle.
If EventRepMode = HiPriSpont, spontaneous events will be delivered prior to GI
event. To prevent old GI data from being delivered after a new spontaneous event,
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN