Section 3
Engineering process
30
•
Build the plant structure according to the substation structure.
•
Insert an IED in plant structure which can be done in many ways. By
inserting the IED in online mode where the configuration is read from
the physical IED, by inserting an IED in offline mode, by importing a
*.pcmi file or by selecting an IED template from the template library
(*.pcmt).
•
Rename the IED objects in PCM600 to the projects definitions.
•
Set the IEC 61850 technical key (or use the default one from PCM600).
•
ECT Ethernet configuration
•
Configure the access points, routes and merging units
•
Check and adjust if needed the setting values for example for:
•
Operation of the access points
•
Redundant communication on the access points
•
Route for communication of devices in different subnetworks
•
Operation of merging unit receivers.
•
ACT Application configuration
•
Save the configuration made with ACT to make the interfaces and
signals available for other engineering tools within PCM600, for
example for PST.
•
PST Parameter setting and configuration
•
Check the configuration parameters of the physical IED for
communication channels.
•
Check and adjust the setting values if needed for example for:
•
Presentation parameters for local HMI.
•
Settings for control functions.
•
Number of setting groups.
•
GDE Single line diagram configuration
•
Create a single line diagram.
•
Include measurements when needed.
•
Link the dynamic elements to functions created in ACT, for example a
breaker object to the switch function.
•
Local HMI engineering
•
Include and engineer the function blocks for LHMI element groups with
ACT and SMT.
•
Define the LED behavior with PST.
•
Configure the LEDs with ACT and SMT.
•
Communication protocol engineering
For performance reasons, do not insert more than 40
IEDs in one PCM600 project. Larger projects can be
divided into several PCM600 projects.
1MRK 511 398-UEN C
670 series 2.2 IEC
Engineering manual