Fujitsu AS*G09KXCA Series Service Instruction page 79

Split type room air conditioner wall mounted type inverter
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 3
Outdoor unit Electronic Expansion Valve
( EEV )
Check Point 1 : Check Connections
Check connection of connector
( Loose connector or open cable )
EXPANSION
VALVE COIL
RED
1
BLUE
2
ORANGE
EV
P30
3
YELLOW
4
WHITE
5
Check Point 2 : Check Coil of EEV
Remove connector, check each winding
resistance of Coil.
Read wire
White - Red
Yellow - Red
46
Orange - Red
Blue - Red
If Resistance value is abnormal, replace EEV.
Check Point 5 : Check Opening and Closing Operation of Valve
When Valve is closed,
it has a temp. difference between Inlet and Outlet.
CLOSE
Example : Hot Gas
Pipe (In)
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in
but if there is a difference as shown in
Pipe (In)
Resistance value
4
at 20°C
Pipe (Out)
, there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (Out)
Check Point 3 : Check Voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Check Point 4 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show,
replace Main PCB.
If it is open,
it has no temp. difference between Inlet and Outlet.
OPEN
Example : Hot Gas
Pipe (In)
Pipe (In)
02-45
DC
Pipe (Out)
,
Pipe (Out)