Fujitsu AS*G09KXCA Series Service Instruction page 55

Split type room air conditioner wall mounted type inverter
Table of Contents

Advertisement

Trouble shooting 18
OUTDOOR UNIT Error Method:
Outdoor Thermistor Error
Detective Actuators:
Outdoor unit Main PCB
Outdoor temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
Temperature
(°C )
Resistance value (k )
Temperature
(°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
BLACK
Thermistor (Outdoor temp.)
1
1
P5
2
2
BLACK
3
3
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Indoor Unit :
Operation indicator : 7 times Flash
Timer indicator
Economy indicator: Continuous Flash
Error code : [ E: 74 ]
Detective details:
When Outdoor temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
2. Thermistor failure
-30
-20
-10
-5
224.3
115.2
62.3
46.6
20
30
40
50
12.6
8.0
5.2
3.5
02-22
: 4 times Flash
3. Main PCB failure
0
5
10
15
35.2
26.9
20.7
16.1
60
70
80
2.4
1.7
1.2