Fujitsu AS*G09KXCA Series Service Instruction page 108

Split type room air conditioner wall mounted type inverter
Table of Contents

Advertisement

Before servicing the unit, turnings of all power supplies.
Then, do not touch the electric parts for 10 minutes due to the risk of electric shock.
3. Remove the Hex socket screw
and compressor terminal cover.
5. Remove the Compressor bolts. ( 3 places )
Cut the Discharge pipe in this range.
CAUTION
・Keep their shape better.
・There is a possibility of catching fire to oil when removing by the welding without cutting it.
4. Remove the connectors.
[ R : White, S : Red, C : Black ]
Tips!
Remove the Compressor bolts anticlockwise direction.
Range
Cut the Suction pipe in this range.
Remove the Compressor.
04-18
Range