Fujitsu AS*G07LUCA Design & Technical Manual
Fujitsu AS*G07LUCA Design & Technical Manual

Fujitsu AS*G07LUCA Design & Technical Manual

Hide thumbs Also See for AS*G07LUCA:

Advertisement

Quick Links

AIR CONDITIONER

Wall Mounted type

DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
AS  G07LUCA
AS  G09LUCA
AS  G12LUCA
AS  G14LUCA
AO  G07LUC
AO  G09LUC
AO  G12LUC
AO  G14LUC

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AS*G07LUCA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Fujitsu AS*G07LUCA

  • Page 1: Air Conditioner

    AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS  G07LUCA AS  G09LUCA AS  G12LUCA AS  G14LUCA OUTDOOR AO  G07LUC AO  G12LUC AO  G09LUC AO  G14LUC...
  • Page 2: Indoor Unit

    1. INDOOR UNIT WALL MOUNTED TYPE : ASG07LUCA ASG09LUCA ASG12LUCA ASG14LUCA DTR_AS053E_01 2011.04.08...
  • Page 3: Table Of Contents

    CONTENTS 1. INDOOR UNIT 1. FEATURE ........................01 - 01 2. WIRELESS REMOTE CONTROLLER ..........01 - 03 3. SPECIFICATIONS ....................01 - 05 4. DIMENSIONS ......................01 - 06 5. WIRING DIAGRAMS ..................01 - 08 6. CAPACITY TABLE ....................
  • Page 4: Feature

    FEATURE MODEL „ „ ASG07LUCA / AOG07LUC ASG09LUCA / AOG09LUC ASG12LUCA / AOG12LUC ASG14LUCA / AOG14LUC AO  G07LUC AO  G12LUC AO  G09LUC AO  G14LUC FEATURES „ „ Energy-Efficiency classification A „ Europe Energy-Efficiency classification A achieved Thin &...
  • Page 5: Economy Operation

    Outdoor unit low noise „ *Only available with Wireless RC. When air-conditioner operates in large capacity, operation noise of outdoor unit will be suppressed. In case of room temperature being close to setting temperature, operation noise might not decrease. Down Low noise Rated noise level...
  • Page 6: Wireless Remote Controller

    WIRELESS REMOTE CONTROLLER FEATURES „ „ 3 Mode timer setup  „ (Weekly / Program / Sleep) are possible. Easy operation.  „ Easy to change signal code (4 patterns) by button operation.  „ Simple function setting „ Setting of the air conditioner selection function is performed by remote controller. Built-in timers „...
  • Page 7 FUNCTIONS „ „ Signal Transmitter MODE button FAN button 10 °C HEAT button ECONOMY button SWING button TEMP. OUTDOOR UNIT LOW button SET button NOISE button POWERFUL button TIMER SETTING button WEEKLY button START/STOP SEND button button ON/OFF button SLEEP button SELECT button RESET button NEXT button...
  • Page 8: Specifications

    SPECIFICATIONS WALL MOUNTED Type INVERTER HEAT PUMP Model name AS  G07LUCA AS  G09LUCA AS  G12LUCA AS  G014LUCA Power source 230V~ 50Hz Available voltage range 198-264V~ 50Hz Cooling European energy label Heating 2.00 2.50 3.50 4.20 Rated BTU/h 6,800 8,500...
  • Page 9: Dimensions

    DIMENSIONS MODEL : ASG07LU, ASG09LU, ASG12LU, ASG14LU „ „ (Unit : mm) 187:Installed state - (01 - 06) -...
  • Page 10 INSTALLATION PLACE „ „ (Unit : mm) - (01 - 07) -...
  • Page 11: Wiring Diagrams

    WIRING DIAGRAMS MODEL : ASG07LU, ASG09LU, ASG12LU, ASG14LU „ „ - (01 - 08) -...
  • Page 12: Capacity Table

    CAPACITY TABLE 6-1. COOLING CAPACITY MODEL : ASG07LU „ „ 11.3 Indoor temperature °CDB °CWB °CDB 1.87 1.32 0.32 2.09 1.33 0.33 2.16 1.45 0.33 2.30 1.45 0.33 2.37 1.57 0.33 2.51 1.56 0.34 2.65 1.66 0.34 1.78 1.26 0.36 1.98 1.26 0.37...
  • Page 13: Heating Capacity

    6-2. HEATING CAPACITY MODEL : ASG07LU „ „ 12.2 Indoor temperature (°CDB) (°CDB) (°CWB) 2.15 0.83 2.10 0.85 2.05 0.87 2.00 0.88 1.95 0.90 2.52 0.88 2.46 0.90 2.40 0.92 2.34 0.94 2.28 0.96 2.77 0.91 2.70 0.93 2.63 0.95 2.57 0.97 2.50...
  • Page 14: Fan Performance

    FAN PERFORMANCE 7-1. AIR VELOCITY DISTRIBUTION Note: Fan speed : High MODEL : ASG07LU „ „ Operation mode : FAN Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Center 0.75 Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Right &...
  • Page 15 Note: Fan speed : High MODEL : ASG09LU „ „ Operation mode : FAN Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Center Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Right & Left Unit : m/s SIDE VIEW Vertical flap : Up...
  • Page 16 Note: Fan speed : High MODEL : ASG12LU, ASG14LU „ „ Operation mode : FAN Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Center Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Right & Left Unit : m/s SIDE VIEW Vertical flap : Up...
  • Page 17: Air Flow

    7-2. AIR FLOW MODEL : ASG07LU „ „ Cooling „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1140 1050 QUIET Heating „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1180 1050 QUIET - (01 - 14) -...
  • Page 18 MODEL : ASG09LU „ „ Cooling „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1300 1080 QUIET Heating „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1300 1120 QUIET - (01 - 15) -...
  • Page 19 MODEL : ASG12LU „ „ Cooling „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1370 1120 QUIET Heating „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1370 1180 QUIET - (01 - 16) -...
  • Page 20 MODEL : ASG14LU „ „ Cooling „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1440 1220 QUIET Heating „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1510 1220 1030 QUIET - (01 - 17) -...
  • Page 21: Operation Noise

    OPERATION NOISE 8-1. NOISE LEVEL CURVE MODEL : ASG07LU „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 High High NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 Quiet Quiet NC-15 NC-15 1,000 2,000...
  • Page 22 MODEL : ASG12LU „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 High NC-45 NC-45 High NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 Quiet Quiet NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 23: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT - (01 - 20) -...
  • Page 24: Electric Characteristics

    ELECTRIC CHARACTERISTICS Model name ASG07LU ASG09LU ASG12LU ASG14LU Voltage 230~ Power supply Frequency Max. operating current Connection cable 1.0-1.5 *1)Wiring Spec. Limited wiring length *1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005) - (01 - 21) -...
  • Page 25: Safety Devices

    SAFETY DEVICES Model ASG07LU Protection form ASG09LU ASG12LU ASG14LU Circuit protection Current fuse (PCB) 3.15A 250V Terminal protection Current (thermal) fuse 3A 250V °C OFF Fan motor protection Thermal protector program °C ON - (01 - 22) -...
  • Page 26: External Input & Output

    EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS CNA01 Control input See external CNB01 Operation status output input/output settings for details. CNB02 Error status output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) „ „ The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
  • Page 27 When function setting is "Forced stop" mode „ Input signal Forced stop Command Normal Operation Indoor unit Stop Remote controller Remote control operation invalidity Parts (Optional) „ Parts name Model name External connect kit UTY-XWZXZ5 Communication kit UTY-TWBXF * For operating the EXTERNAL function, the Compact wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
  • Page 28: External Output

    11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT „ „ An air conditioner operation status signal can be output. Circuit diagram example „ Indoor control PC board Communication kit Connected unit Connector 24V DC Ex.)Relay unit Ex.)Display Relay power supply *10 m Signal Optional parts Field supply...
  • Page 29 ERROR STATUS OUTPUT „ „ An air conditioner error status signal can be output. Circuit diagram example „ Indoor control PC board Communication kit Connected unit Connector 24V DC Ex.)Relay unit Ex.)Display Relay power supply *10 m Signal Optional parts Field supply * Make the distance from the PC board to the connected unit within 10m.
  • Page 30: Function Setting

    FUNCTION SETTING 12-1. INDOOR UNIT (Setting by remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “FUNCTION SETTING”...
  • Page 31: Function Details

    FUNCTION DETAILS „ „ Compact wall Functions mounted 1) Filter sign 2) Cooler room temperature correction 3) Heater room temperature correction 4) Auto restart Indoor room temperature sensor switching function 6) Remote controller signal code 7) External input control 1) Filter sign The indoor unit has a sign to inform the user that it is time to clean the filter.
  • Page 32 4) Auto restart Enable or disable automatic system restart after a power outage. (  ... Factory setting) Setting description Function number Setting value  * Auto restart is an emergency function such as for power failure etc. Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, or external input device.
  • Page 33 REMOTE CONTROLLER SIGNAL CODE SETTING „ „ Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) Press the START/STOP ( / ) button until only the clock is displayed on the remote controller display.
  • Page 34: Optional Parts

    OPTIONAL PARTS Exterior Parts name Model No. Summary Unit control is performed by Wired remote wired remote controller. UTY-RNNYM controller *Optional communication kit is necessary for the installation. Unit control is performed by Simple remote simple remote controller. UTY-RSNYM controller *Optional communication kit is necessary for the installation.
  • Page 35: Outdoor Unit

    2. OUTDOOR UNIT SINGLE TYPE : AOG07LUC AOG09LUC AOG12LUC AOG14LUC DTR_AO085E_01 2011.04.08...
  • Page 36 CONTENTS 2. OUTDOOR UNIT 1. SPECIFICATIONS ....................02 - 01 2. DIMENSIONS ......................02 - 02 3. REFRIGERANT CIRCUIT ................02 - 04 4. WIRING DIAGRAMS ..................02 - 05 5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE ..................
  • Page 37: Specifications

    SPECIFICATIONS Type INVERTER COOLING & HEATING Model name AO  G07LUC AO  G09LUC AO  G12LUC AO  G14LUC Power source 230V~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current Cooling 1,720 1,720 1,940 1,940 Airflow rate Heating 1,510 1,510 1,700...
  • Page 38: Dimensions

    DIMENSIONS MODEL : AOG07LU, AOG09LU „ „ (Unit : mm) Top view Front view Side view Air flow Bottom view INSTALLATION PLACE „ „ When there are obstacles at When there are obstacles at When there are obstacles at the the back or front sides.
  • Page 39 MODEL : AOG12LU, AOG14LU „ „ (Unit : mm) Top view Front view Side view Air flow Drain pipe 4-ø11.3mm hole mounting place (ø20) Bottom view INSTALLATION PLACE „ „ When there are obstacles at When there are obstacles at When there are obstacles at the the back or front sides.
  • Page 40: Refrigerant Circuit

    REFRIGERANT CIRCUIT MODEL : AOG07LU, AOG09LU, AOG12LU, AOG14LU „ „ Heat exchanger 3-Way ( INDOOR ) valve 2-Way valve Muffler 4-Way valve Strainer Expansion valve Heat exchanger Strainer ( OUTDOOR ) Cooling Heating Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8"...
  • Page 41: Wiring Diagrams

    WIRING DIAGRAMS MODEL : AOG07LU, AOG09LU „ „ - (02 - 05) -...
  • Page 42 MODEL : AOG12LU, AOG14LU „ „ - (02 - 06) -...
  • Page 43: Capacity Compensation Rate For Pipe Length And Height Difference

    CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE MODEL : AOG07LU „ „ Pipe length (m) COOLING 0.872 0.910 Û 1 0.961 0.886 0.925 Indoor unit is upper than 0.979 0.965 0.890 0.929 outdoor unit. 0.992 0.983 0.969 0.893 0.933 Height difference H...
  • Page 44 MODEL : AOG09LU, AOG12LU „ „ Pipe length (m) COOLING 0.858 0.868 Û 1 0.929 0.872 0.882 Indoor unit is upper than 0.960 0.933 0.876 0.885 outdoor unit. 0.992 0.964 0.937 0.879 0.889 Height difference H 1.000 0.972 0.944 0.887 0.896 1.000 0.972...
  • Page 45 MODEL : AOG14LU „ „ Pipe length (m) COOLING 0.893 0.909 Û 1 0.955 0.908 0.924 Indoor unit is upper than 0.975 0.959 0.912 0.928 outdoor unit. 0.992 0.979 0.963 0.916 0.931 Height difference H 1.000 0.987 0.970 0.923 0.939 1.000 0.987 0.970...
  • Page 46: Additional Charge Calculation

    ADDITIONAL CHARGE CALCULATION MODEL : AOG07LU „ „ Refrigerant type R410A Refrigerant amount Refrigerant charge „ Total pipe length 15 or less 20 (MAX) 20g/m Additional charge MODEL : AOG09LU „ „ Refrigerant type R410A Refrigerant amount Refrigerant charge „ Total pipe length 15 or less 20 (MAX)
  • Page 47: Air Flow

    AIR FLOW MODEL : AOG07LU „ „ Cooling „ Number of rotations Air flow (r.p.m.) 1720 1012 Heating „ Number of rotations Air flow (r.p.m.) 1510 MODEL : AOG09LU „ „ Cooling „ Number of rotations Air flow (r.p.m.) 1720 1012 Heating „...
  • Page 48 MODEL : AOG12LU „ „ Cooling „ Number of rotations Air flow (r.p.m.) 1940 1141 Heating „ Number of rotations Air flow (r.p.m.) 1700 1000 MODEL : AOG14LU „ „ Cooling „ Number of rotations Air flow (r.p.m.) 1940 1141 Heating „...
  • Page 49: Operation Noise

    OPERATION NOISE 8-1. NOISE LEVEL CURVE MODEL : AOG07LU „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 50 MODEL : AOG12LU „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency,Hz Octave band center frequency,Hz MODEL : AOG14LU...
  • Page 51: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT - (02 - 15) -...
  • Page 52: Electric Characteristics

    ELECTRIC CHARACTERISTICS Model name AO  G07LU AO  G09LU AO  G12LU AO  G14LU Voltage 230 ~ Power supply Frequency *1) Max operating current 10.5 Starting Current Main Fuse (Circuit breaker) Current *2) Wiring Spec.: Power Cable *3) Limited wiring length : *1) The maximum current is the total current of indoor unit and outdoor unit.
  • Page 53: Safety Devices

    SAFETY DEVICES Model Protection form AO  G07LU AO  G09LU AO  G12LU AO  G14LU Current fuse 20A/250V Circuit protection (MAIN PRINTED 5A/250V CIRCUIT BOARD) Thermal protection OFF : 100 °C Fan motor protection program ON : 95 °C Terminal protection program OFF:110°C...