Trouble shooting 17
OUTDOOR UNIT Error Method:
Heat Ex. Liquid Outlet Thermistor Error
Detective Actuators:
Outdoor unit Main PCB
Heat exchanger temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
Temperature
(°C )
Resistance value (k )
Temperature
(°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
BLACK
1
1
Thermistor (PIPE temp.)
BLACK
2
2
P1
BLACK
3
3
BLACK
4
4
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Indoor Unit :
Operation indicator: 7 time Flash
Timer indicator
Economy indicator: Continuous Flash
Error code: [ E : 73 ]
Detective details:
When Heat exchanger temperature thermistor open or
short-circuit is detected at power ON or while running the compressor.
2. Thermistor failure
-30
-20
-10
-5
92.3
49.2
27.5
20.9
20
30
40
50
6.1
4.0
2.6
1.8
02-21
: 3 time Flash
3. Main PCB failure
0
5
10
15
16.1
12.4
9.7
7.7
60
70
80
90
1.3
0.9
0.7
0.5