Auto Changeover Operation - Fujitsu AS*G09KXCA Series Service Instruction

Split type room air conditioner wall mounted type inverter
Table of Contents

Advertisement

4. AUTO CHANGEOVER OPERATION

When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum
mode from among the Heating, Cooling, and Monitoring mode. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1.0°C steps.
When operation starts, indoor main fan and outdoor fan are operated for around 1 minutes.
1
Room temperature and outdoor temperature are sensed, and the operation mode is selected
in accordance with the table below. <Monitoring mode>
( Table 4 : Operation mode selection table )
Room temperature (TR)
TR> Ts+2°C
Ts+2°C
TR < Ts -2°C
*
If it's Middle zone, operation mode of indoor unit is selected as below.
(1). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling and Heating mode, indoor unit will be operated
according to the outdoor temperature as below.
( Fig.3 : Outdoor temperature zone selection )
Temperature
25
and over
°C
25
under
°C
2
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the Cooling or Heating mode was selected at
to Monitoring and the operation mode is selected again.
When the middle zone is selected on the predetermining of the operation mode, the operation mode
3
before the changing to the monitor mode is selected.
Operation mode
*
TR
Ts -2°C
Mode
Cooling
Heating
01-03
TR : Room temperature
Ts : Setting temperature
Cooling
Middle zone
Heating
1
above, operation is switched